2 Introduction:
The LQ10/LQ25 series voltage regulator for direct action type two level balance regulator. Widely used for industrial users and commercial users of natural gas, liquefied petroleum gas or other non-corrosive gas transmission and distribution. Built-in filtering. Bleeding valve for overpressure protection device is cut off. Has the advantages of small size and easy installation. The stable pressure responsive and so.
|
2 Technical parameters:
The maximum inlet pressure /P1max:6bar
Inlet pressure range /δ P1: 0.6-6bar
Outlet pressure range of δ P2:15-70mbar / standard type
/ high-voltage Delta P2:70-300mbar
Accuracy of ± 10% /AC:
Closing pressure /SG: ≤ 20%
The cutting accuracy of ± 5% /AQ:
Response time is /ta:≤ 1sec
The maximum flow rate ( NG ) /Qmax:70Nm3/h
Working temperature: -20~+60 ℃
|
|