2 Introduction:
The LT17 series voltage regulator for the direct effect of the diaphragm and the spring control regulator. Suitable for the area medium-sized commercial facilities, pressure. Built-in valve, high and low pressure safety protection device. Has the characteristics of simple structure, convenient operation, convenient maintenance, on-line.
|
2 Technical parameters:
The maximum inlet pressure /P1max:6bar
Inlet pressure range /δ P1:0.5-5bar
Outlet pressure range / standardδ P2:15 ~ 70mbar
High P2:70 δ~ 300mbar
Overpressure cutting set pressure Who:22.5~450mbar
Low cut set pressure Whu:12.8~250mbar
Accuracy of ± 8% /AC:
Closing pressure: /SG≤ 20%
The cutting accuracy of ± 5% /AQ:
Response time: /ta≤ 1sec
The maximum flow rate ( NG ) /Qmax:300Nm3/h
Working temperature: -20 ~ +60 ℃
Connecting dimensions: RP1 1/2 "
Weight: low voltage 4.8kg high voltage type 6kg;
|
|