2 Brief
It is suitable for kinds of city gas transmission and distribution system for pressure regulation and stabilization, and it is used to regulate pressure for residential quarters’ users, small-size public welfare users and gas boiler etc. and it can be refitted into wall-mounted pressure regulator box or floor-type pressure regulator cabinet.
Features
Stable performance, good adaptability, automatically shut off for limiting pressure.
2 Technical Parameters
Inlet pressure range: P1 0.02~0.4MPa
Outlet pressure range: P2 1~30KPa (adjustable)
Pressure precision: δP≤±15%
Closing pressure: ≤1.25P2
MAX. Flow: Q=860Nm3/h
Caliber: DN40, DN50, DN80 (Flange PN1.6)
|
|