CLRX Series Gas Regulator Boiler Cabinet |
| |
|
|
|
| |
2 Application
CLRX series gas regulator boiler cabinet has the function of regulation, filter, overpressure cut-off, measurement and safety divergence. It is usually structured in cabinet, it has little requirement for floor area and has attractive appearance, so it’s suited to installed either indoor or outdoor.
It is applicable for natural gas and artificial coal gas. |
|
| |
|
|
|
|
 |
 |
 |
| |
|
|
|
| |
2 Features
Inlet Pressure Rank (P1): 0.05~0.4MPa (Natural Gas)
0.03~0.1MPa(Artificial Coal Gas)
Outlet Pressure Rank (P2):5~15KPa
Pressure Precision Grade: AC5
Shut Off Pressure Grade: SG10
2 Basic Configuration
CLRX series gas regulator cabinet mainly consists of inlet/outlet valve, gas filter, gas regulator, emergency shut-off valve, measurement instrument and safety bleeding valve etc.
|
 |
|
| |
|
|
|
|
|  Reference |
Order |
Model |
Inlet pressure(MPa) |
outlet pressure(KPa) |
Rated Flow
(Nm3/h) |
Suitable boiler |
Natural gas |
Artificial Coal gas |
 1 |
CLRX-100﹡﹡ |
0.03~0.4 |
1~15 |
100 |
0.5T, 1T boiler |
0.5T boiler |
 2 |
CLRX-200﹡﹡ |
0.03~0.4 |
5~15 |
200 |
1.5T,2T boiler or gross tonnage ≤2T boiler group |
1T boiler |
 3 |
CLRX-400﹡﹡ |
0.03~0.4 |
5~15 |
400 |
2.5T,3T,4T boiler or gross tonnage≤4T boiler group |
1.5T,2T boiler or gross tonnage ≤2T boiler group |
 4 |
CLRX-600﹡﹡ |
0.03~0.4 |
5~15 |
600 |
5T,6T,8T boiler or gross tonnage ≤8T,a single piece≥1T boiler group |
2.5T,3T,4T boiler or gross tonnage≤4T boiler group |
 5 |
CLRX-1000﹡﹡ |
0.03~0.4 |
5~15 |
1000 |
10T,15T boiler or gross tonnage ≤15T,a single piece≥2T boiler group |
5T,6T,8T boiler or gross tonnage ≤8T,a single piece≥1T boiler group |
 6 |
CLRX-2000﹡﹡ |
0.03~0.4 |
5~15 |
2000 |
20T,25T boiler or gross tonnage ≤25T,a single piece≥3T boiler group |
8T,10T boiler or gross tonnage ≤10T,a single piece≥2T boiler group |
 7 |
CLRX-3000﹡﹡ |
0.03~0.4 |
5~15 |
3000 |
30T boiler or gross tonnage ≤30T,a single piece≥4T boiler group |
15T boiler or gross tonnage ≤15T,a single piece≥3T boiler group |
|
| |
|
|
|
| |
2 (Note: The rated flow mentioned above means the gas flow under the standard state and the inlet pressure is 0.2MPa, density is 0.61 and artificial coal gas’ conversion coefficient is 1.17. The choice should be on the basic of the actual inlet/outlet pressure, media and gas’ heat value as well as the description for regulator.)
|
|
| |
|
|
|
|
| |
| |
| BACK |
| |